Maximum underfloor heating loop length

A loop that is too long has too much flow resistance: the pump cannot push enough water through it, and the far end stays cooler. That is why every loop has a length limit.

Recommended lengths

Pipe (outer diameter)Longest loopArea per loop at 15 cm spacing
16 mmup to 100 mabout 12–14 m²
17 mmup to 120 mabout 15–16 m²
20 mmup to 120 mabout 15–16 m²

The loop length includes the leads to the manifold. The further away the room, the less pipe is left for the room itself.

Most manufacturers give similar limits, but check your pipe's data sheet for the exact figure. Cautious designers use 80–90 m for 16 mm pipe.

Split large rooms into several loops

If a room needs more pipe than fits in one loop, it is split into two or more. It is best when they are of similar length: they are easier to balance at the manifold, and the floor warms evenly.

Why loops should be of similar length

Water takes the path of least resistance. A short loop gets too much water, a long one too little. The flow regulators on the manifold even this out, but only up to a point. The closer the loop lengths, the easier the system is to balance.